Filter Fan Plus
FPI/FPO 018 | up to 727 m³/h (291 x 291 mm)

  • New air-flap outlet technology for high airflow
  • Easy mounting
  • Protection type test/Environmental rating by independent testing institutes (VDE & UL)
  • Two systems for optimal airflow (FPI/FPO)
  • Standard enclosure cut-out sizes (5 sizes)
  • One filter mat

Filter fans are used to provide an optimum climate in enclosures and cabinets with electrical/electronic components. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting airflow prevents formation of localised hot pockets in installations and protects electronic components from overheating.

The Filter Fan Plus series uses a new airflap-outlet technology for the air outlet and thus reaches a high degree of airflow. A ratchet mechanism is used for mounting and provides high stability and tightness. Depending on the application there are two systems that are available - the FPI or FPO system. The FPI system is a standard installation with a filter fan in the lower part of the enclosure which ensures that fresh air is fed into the enclosure (airflow direction "In"). This system consists of a filter fan and exit filter. Whereas in the FPO system, the filter fan is located in the upper area of the enclosure to avoid heat buildups (airflow direction "Out"). The FPO system is composed of an intake filter and exit filter fan. The Filter Fan Plus series has been designed for indoor use.

Technical Data

Download PDF

Axial fan, ball bearingservice life L10 at +40 °C (+104 °F): min. 76,000 h
rotor metal
Connection3-pole clamp for 2.5 mm², clamping torque 0.8 Nm max.
Casing, hood, flapsplastic according to UL94 V-0, light grey;
UV light resistant according to UL746C (f1)
Enclosure cut-out291 x 291+1 mm
Mounting frame4 built-in ratchet braces for mounting
(6 notches for wall thickness 1-4 mm).
Additional use of screws possible if needed1.
Filter matG3 acc. to DIN EN 779, average arrestance Aa 84 %
Filter materialsynthetic fibre with progressive construction, temperature
resistant to +100°C, self-extinguishing class F1,
moisture resistant to 100% RH, reusable
Operating temperature50 Hz: -25 to +55 °C (-13 to +131 °F)
60 Hz: -25 to +35 °C (-13 to +95 °F)
Storage temperature-40 to +70 °C (-40 to +158 °F)
Operating/Storage humiditymax. 75 % RH (non-condensing)
Protection type/Protection classIP54 / I (earthed)
Environmental rating UL/NEMAUL TYPE 12 / NEMA 12
ApprovalsVDE, UL File No. E234324, EAC
Noteother voltages on request

1 Drilling marks for screw mounting are indicated on mounting frame.

Airflow direction "In": Filter Fan FPI 018

Art. No.Operating voltageAir volume,
free flow
Air volume
with exit filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Filter mat
01874.0-30AC 230 V, 50/60 Hz433 m³/h373 m³/h400/480 mA95 W62 dB (A)160 mm3.1 kgG3
01874.9-30AC 115 V, 50/60 Hz394 m³/h339 m³/h660/800 mA90 W61 dB (A)160 mm3.1 kgG3

Airflow direction "In": Exit Filter FPI 118

Art. No.Depth in enclosureWeight (approx.)Air outlet
11874.0-0050 mm1.0 kgair-flap outlet technology

To top

Airflow direction "Out": Filter Fan FPO 018

Art. No.Operating
voltage
Air volume,
free flow
Air volume
with intake filter
Current
consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01884.0-00AC 230 V, 50/60 Hz727 m³/h413 m³/h400/480 mA95 W63 dB (A)160 mm3.2 kgair-flaps
01884.9-00AC 115 V, 50/60 Hz703 m³/h391 m³/h660/800 mA90 W62 dB (A)160 mm3.2 kgair-flaps

Airflow direction "Out": Intake Filter FPO 118

Art. No.Depth in enclosureWeight (approx.)Filter mat
11884.0-3025 mm0.8 kgG3 acc. to DIN EN 779, average arrestance Aa 84 %

Filter Mat FM 086

Filter class283 x 283 mmAverage arrestance Aa1 packaging unit
G3 acc. to DIN EN 779Art. No. 08637.0-0084 %5 pieces

To top

Technical Drawings

FPI 018/FPI 118
FPO 018/FPO 118