Hazardous Area Thermostat
REx 011 | 15°C, 25°C

  • Compact design
  • Set temperature
  • High switching capacity

Compact small mechanical thermostat for temperature regulation and monitoring of heaters, for example in transmitter cabinets, control panels and measuring equipment which are deployed in areas with explosion hazard. The special switch construction enables high response accuracy, small switch temperature difference and a very long service life. High switching performance allows direct control of the heaters.

Technical Data

Download PDF

Sensor elementthermostatic bimetal
Contact type (1-pole)opens with rising temperature
Service life> 100 000 cycles
Max. switching capacity250VAC, 1.3 (0.65) A
Max. inrush currentAC 4A for 12 sec.
ConnectionSi HF - JZ 3 x 0.75mm², length 1m
Mountingmounting bracket with nut M8 (see illustration)
Casingaluminium, black anodised
Dimensionslength 110mm
Weightapprox. 0.2kg
Fitting positionvariable
Storage temperature-45 to +70°C (-49 to +158°F)
Operating/Storage humiditymax. 90% RH (non-condensing)
Protection type/Protection classIP6X / I (earthed)

LCIE 01 ATEX 6074
IECEx LCI 07.0021

Art. No.Ambient
Ex protection type
Ex II 2 GD
Gases           Dusts
Switch-off temperatureSwitch temperature difference
01180.0-00-40 to +60°C (-40 to +140°F)Ex d IIC T6 GbEx tb IIIC T85°C Db IP6X+15°C (±4K tolerance)4K (±1K tolerance)
01181.0-00-40 to +60°C (-40 to +140°F)Ex d IIC T6 GbEx tb IIIC T85°C Db IP6X+25°C (±4K tolerance)4K (±1K tolerance)

To top

¹ Ambient temperature inside of the cabinet/enclosure

To top