RFP 018 Roof Filter Fan Series

  • Very low noise
  • Minimal mounting depth
  • High air volume
  • High reliability
  • Time-saving installation

Roof filter fans and roof exhaust filters are used in enclosures from which warm air must be diverted due to increased heat development.  The ready-to-connect and low-noise roof filter fan is used to expel warm air from within the enclosure.  Alternatively, the roof exhaust filter provides passive ventilation.  The RFP 018 series comes in two versions:  one utilizes four small axial fans, improving reliability and maintaining continuous operations even if one of the fans
should fail;  the second uses a larger single high capacity fan.

>>Download PDF                       >>Download CAD PDF

Axial fans, ball bearing service life min. 50,000h at 77°F (25°C) and 65% RH
  aluminum fan body, plastic rotor
Connection 3-pole clamp, AWG 14 (2.5mm²), clamping torque 0.8Nm max.
Housing Plastic, UL 94V-0, light grey; weather and UV light resistant according to UL 746C (f1)
Filter mat G3 acc. to DIN EN 779, filtering degree 85%
Filter material synthetic fiber with progressive construction, temperature resistant to 100°C, self-extinguishing class F1; moisture resistant to 100% RH, reusable - can be cleaned by washing or vacuuming
Operating / Storage temperature -4 to +158°F (-45 to +70°C)
Protection class I (grounded)
Protection type IP43 (with G3 filter mat) / IP33 (without filter mat)
Approvals UL and VDE intended

Important note:  For reasons of pressure compensation, the roof filter fan must always be operated in combination with another filter fan (e.g. Part No. 01803.0-00) or a passive intake filter (e.g. Part No. 11803.0-00).

To top

Part. No. Operating voltage Air volume, free blowing (w/ G3 filter mat) Air volume, free blowing (w/out filter mat) Power consumption Average noise level (DIN EN ISO 4871) Mounting depth Enclosure cut-out Weight (approx.)
01860.0-00 230VAC, 50Hz¹ 177 cfm (300m³/h) 235 cfm (400m³/h) 68W 55db (A) 2.0” (52mm) 9.8 x 9.8” 7.3 lbs. (3.3kg)
01860.0-02 120VAC, 60Hz 203 cfm (345m³/h) 271 cfm (460m³/h) 60W 55db (A) 2.0” (52mm) 9.8 x 9.8” 7.3 lbs. (3.3kg)
01861.0-00 230VAC, 50Hz¹ 294 cfm (500m³/h) 383 cfm (650m³/h) 64W 67db (A) 4.2” (107mm) 9.8 x 9.8” 5.7 lbs. (2.6kg)
01861.0-02 120VAC, 60Hz 338 cfm (575m³/h) 440 cfm (748m³/h) 85W 67db (A) 4.2” (107mm) 9.8 x 9.8” 5.7 lbs. (2.6kg)

¹)air volume increases by 15% when operating 230VAC filter fans at 60HZ

To top

REP 118 Roof Exhaust Filter

Part. No. Mounting depth Enclosure cut-out Weight (approx.) Filter mat Protection type
11860.0-00 0.43” (11mm) 9.8 x 9.8” 2.2 lbs. (1.0kg) G3 acc. to DIN EN 779, filtering degree 85% IP43 (w/ G3 filter mat)

FM 086 Filter Mats

Filter mat 11.1 x 11.1” (282 x 282 mm)
G3 (1 packing unit = 3 pcs.) Part. No. 08613.0-00

To top

Technical drawing

To top

Search 

STEGO, Inc.

1395 South Marietta Parkway
Building 800
Marietta, GA 30067
USA

Telephone (770) 984-0858
Toll-free    (888) 783-4611
Fax           (770) 984-0615

E-Mail: info(at)stegousa.com

Last updated: 21. May 2012 14:26

Patent Info | Legal Notices | Search engine | Sitemap