Filter Fan FF 018
- Minimal mounting depth
- High air volume
- Functional design
- Time-saving installation
- Weather and UV resistant
Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channeling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localized heat pockets and protects the electronic components from overheating. Four integrated axial fans provide a particularly high and uniform air circulation which contributes to higher reliability. The plastic used for the hood of this filter fan series is highly weather and UV light resistant.
Technical Data
>> Download PDF >> Download CAD Drawing
| Axial fan, ball bearing | service life min. 50,000h at 77°F (25°C) and 65% RH aluminum fan body, plastic rotor |
| Connection | 3-pole clamp, AWG 14 (2.5mm²), clamping torque 0.8Nm max. |
| Housing (filter fan and exhaust filter) | Plastic, UL 94V-0, light grey |
| Hood (filter fan and exhaust filter) | Plastic, UL 94V-0, light grey; weather and UV light resistant according to UL 746C (f1) |
| Mounting frame | with double-sided industrial adhesive for mounting to the outside of enclosure; certain operating circumstances may make the additional use of screws necessary; cut-out template included |
| Filter media rating | G4 acc. to DIN EN 779, filtering degree 94% |
| Filter material | synthetic fiber with progressive construction, temperature resistant to 212°F, self-extinguishing class F1; moisture resistant to 100% RH, reusable - can be cleaned by washing or vacuuming |
| Operating / Storage temperature | -4 to +158°F (-20 to +70°C) |
| Protection class | I (grounded) |
| Protection type | IP55* |
*according to VDE
Note: EMC versions and other voltages are available upon request
| Part No. | Operating voltage | Air volume, free blowing | Air volume with exhaust filter | Power consumption | Average noise level (DIN EN ISO 4871) | Mounting depth | Enclosure cut-out | Weight (approx.) | Approvals |
| 01803.0-00 | 230VAC, 50Hz¹ | 177 cfm (300m³/h) | 135 cfm (230m³/h) | 60W | 53dB (A) | 2.6” (65mm) | 9.8 x 9.8” | 7.3 lbs. (3.30kg) | UL File No. E234324 |
| 01803.0-01 | 120VAC, 60Hz | 202 cfm (345m³/h) | 156 cfm (265m³/h) | 60W | 53dB (A) | 2.6” (65mm) | 9.8 x 9.8” | 7.3 lbs. (3.30kg) | UL File No. E234324 |
¹)air volume increases by 15% when operating 230VAC filter fans at 60Hz
EF 118 Exhaust Filter
| Part. No. | Mounting depth | Enclosure cut-out | Weight (approx.) | Filter mat | Protection type |
| 11803.0-00 | 0.9” (22mm) | 9.8 x 9.8” | 2.2 lbs. (1.0kg) | G4 acc. to DIN EN 779, filtering degree 94% | IP55* |
*accoring to VDE
FM 086 Filter Mats
| Filter mat | 9.7 x 9.7” (247 x 247mm) |
| G4 (1 packing unit = 3 pcs.) | Part No. 08608.0-00 |
| F5 (1 packing unit = 3 pcs.) | Part No. 08609.0-00 |