  • Weather and UV resistant

Filter fans are used to provide an optimum climate in enclosures.  The interior temperature of an enclosure can be reduced by channeling cooler filtered outside air into the enclosure thus expelling heated internal air.  The resulting air flow prevents formation of localized heat pockets and protects the electronic components from overheating.  Four integrated axial fans provide a particularly high and uniform air circulation which contributes to higher reliability.  The plastic used for the hood of this filter fan series is highly weather and UV light resistant.

 

Technical Data

>> Download PDF                       >> Download CAD Drawing

Axial fan, ball bearing service life min. 50,000h at 77°F (25°C) and 65% RH aluminum fan body, plastic rotor
Connection 3-pole clamp, AWG 14 (2.5mm²), clamping torque 0.8Nm max.
Housing (filter fan and exhaust filter) Plastic, UL 94V-0, light grey
Hood (filter fan and exhaust filter) Plastic, UL 94V-0, light grey; weather and UV light resistant according to UL 746C (f1)
Mounting frame with double-sided industrial adhesive for mounting to the outside of enclosure; certain operating circumstances may make the additional use of screws necessary; cut-out template included
Filter media rating G4 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fiber with progressive construction, temperature resistant to 212°F, self-extinguishing class F1; moisture resistant to 100% RH, reusable - can be cleaned by washing or vacuuming
Operating / Storage temperature -4 to +158°F (-20 to +70°C)
Protection class I (grounded)
Protection type IP55*

*according to VDE
Note:  EMC versions and other voltages are available upon request

To top

Part No. Operating voltage Air volume, free blowing Air volume with exhaust filter Power consumption Average noise level (DIN EN ISO 4871) Mounting depth Enclosure cut-out Weight (approx.) Approvals
01803.0-00 230VAC, 50Hz¹ 177 cfm (300m³/h) 135 cfm (230m³/h) 60W 53dB (A) 2.6” (65mm) 9.8 x 9.8” 7.3 lbs. (3.30kg) UL File No. E234324
01803.0-01 120VAC, 60Hz 202 cfm (345m³/h) 156 cfm (265m³/h) 60W 53dB (A) 2.6” (65mm) 9.8 x 9.8” 7.3 lbs. (3.30kg) UL File No. E234324

¹)air volume increases by 15% when operating 230VAC filter fans at 60Hz

To top

EF 118 Exhaust Filter

Part. No. Mounting depth Enclosure cut-out Weight (approx.) Filter mat Protection type
11803.0-00 0.9” (22mm) 9.8 x 9.8” 2.2 lbs. (1.0kg) G4 acc. to DIN EN 779, filtering degree 94% IP55*

*accoring to VDE

FM 086 Filter Mats

Filter mat 9.7 x 9.7” (247 x 247mm)
G4 (1 packing unit = 3 pcs.) Part No. 08608.0-00
F5 (1 packing unit = 3 pcs.) Part No. 08609.0-00

To top

Dimensioned Drawing

Filter Fan FF 018