FZK 011 Mechanical Thermostat
- Wide adjustment range
- High switching capacity
- SPDT (change-over) contact
- Very low hysteresis option
- DIN rail mountable
The FZK 011 mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices where a higher degree of sensing accuracy is required. An integrated resistor (RF) can be connected to improve the switch temperature difference (see Option note).
The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact.
>> Download PDF >> Download CAD Drawing
| Switching difference | approx. 9°F (5K), tolerance -5.4/+3.6°F (-3/+2K) |
| Option note: | connecting terminal “N” (RF heating resistor) enables thermal feedback, reducing the hysteresis - amount is subject to surrounding conditions TBD for each individual application |
| Sensor element | thermostatic bimetal |
| Contact type | SPDT / change-over contact |
| Contact resistance | <10mΩ |
| Service life | > 100,000 cycles |
| Max. switching capacity, NC | 10A resistive / 4A inductive @ 120VAC |
| 10A resistive / 4A inductive @ 250VAC | |
| DC 30W | |
| Max. switching capacity, NO | 5A resistive / 2A inductive @ 120VAC |
| 5A resistive / 2A inductive @ 250VAC | |
| DC 30W | |
| Minimum load | 20mA (all voltages) |
| Connection | 4-pole terminal, clamping torque 0.5Nm max.:solid wire - AWG 14 max. (2.5mm²) stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm²) |
| Housing | plastic, UL 94V-0, light grey |
| Mounting | clip for 35mm DIN rail, EN 60 715 |
| Mounting position | vertical |
| Operating / storage temperature | -49 to +149°F (-40 to +65°C) |
| Dimensions | 2.64 x 1.97 x 1.5” (67 x 50 x 38mm) |
| Weight | approx. 3.5 oz. (100g) |
| Protection type | IP20 |
| Part No. | Operating voltage¹ | Setting range | Approvals |
| 01170.0-00 | 230VAC | 5 to 60°C | UL File No. E164102 |
| 01170.0-01 | 230VAC | 40 to 140°F | UL File No. E164102 |
| 01170.9-00 | 120VAC | 40 to 140°F | UL File No. E164102 |
| 01170.9-01 | 120VAC | 5 to 60°C | UL File No. E164102 |
¹) Voltage only needs to be specified if the optional use of the RF resistor is desired