Filter Fan FF 018 Series | 300m³/h

  • Very low noise
  • Minimal depth in enclosure
  • High through-flow air volume
  • Uniform air circulation
  • High reliability
  • Weather proof and UV resistant

Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localised hot pockets and protects the electronic components from overheating. Four integrated axial fans provide a particularly high and uniform air circulation thus contributing to higher reliability. The plastic used for the hood of this filter fan series is highly weather proof and UV light resistant.

Technical Data

>> Download PDF

Axial fans, ball bearing service life 50,000h at 25°C / 77°F (65% RH)
  fan body aluminium, rotor plastic
Connection 3-pole clamp for 2.5mm², clamping torque 0.8Nm max.
Casing (filter fan and exit filter) plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter) plastic according to UL94 V-0, light grey;
  weather proof and UV light resistant according to UL746C (f1)
Mounting frame with double-sided industrial adhesive band for fixing to the
  outside of enclosure; certain operating circumstances can
  make the additional use of screws necessary (see drilling
  template); a template for the enclosure cut-out is included in the
  delivery of the filter fans
Filter mat G4 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fibre with progressive construction; temperature
  resistant to 100°C, self-extinguishing class F1,
  moisture resistant to 100% RH, reusable - cleaning by
  washing or vacuuming
Operating / Storage temperature -10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating / Storage humidity max. 90% RH (non-condensing)
Protection type / Protection class IP55 / I (earthed)

To top

Filter Fan FF 018 Series

Art. No. Operating voltage Air volume, free flow Air volume with exit filter Current consumption Power consumption Average noise level (DIN EN ISO 4871) Depth in enclosure Enclosure cut-out Weight (approx.) Approvals
01803.0-00 230VAC, 50Hz 300m³/h 230m³/h 400mA 60W 53db (A) 65mm 250 x 250mm + 0.4 3.3kg UL File No. E234324
01803.0-01 120VAC, 60Hz 345m³/h 264m³/h 700mA 60W 53db (A) 65mm 250 x 250mm + 0.4 3.3kg UL File No. E234324

To top

Exit Filter EF 118 Series

Art. No. Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type
11803.0-00 22mm 250 x 250mm + 0.4 1.0kg G4 acc. to DIN EN 779, filtering degree 94% IP55

To top

Filter Mat FM 086

Filter mat 247 x 247mm
G4 (1 packing unit = 3 pcs.) Art. No. 08608.0-00

To top

Technical Drawing

Filter Fan FF 018 Series

To top