Filter Fan FF 018 Series | 21m³/h to 102m³/h

  • Very low noise
  • Minimal depth in enclosure
  • Functional design
  • Time-saving installation
  • Weather proof and UV resistant

Filter fans are used to provide an optimum climate in enclosures. The interior temperature of an enclosure can be reduced by channelling cooler filtered outside air into the enclosure thus expelling heated internal air. The resulting air flow prevents formation of localised hot pockets and protects the electronic components from overheating. The plastic used for the hood of this filter fan series is highly weather proof and UV light resistant. 

Technical Data

>> Download PDF

Axial fan, ball bearing service life 50,000h at 25°C / 77°F (65% RH)
  fan body aluminium, rotor plastic
Connection 2 wires with pressure clamps 2.5mm², length 100mm
Casing (filter fan and exit filter) plastic according to UL94 V-0, light grey
Hood (filter fan and exit filter) plastic according to UL94 V-0, light grey;
  weather proof and UV light resistant according to UL746C (f1)
Mounting frame with double-sided industrial adhesive band for fixing to the
  outside of enclosure; certain operating circumstances can
  make the additional use of screws necessary (see drilling
  template); a template for the enclosure cut-out is included
  in the delivery of the filter fans
Filter mat G4 acc. to DIN EN 779, filtering degree 94%
Filter material synthetic fibre with progressive construction; temperature
  resistant to 100°C, self-extinguishing class F1,
  moisture resistant to 100% RH, reusable - cleaning by
  washing or vacuuming
Operating / Storage temperature -10 to +70°C (+14 to +158°F) / -40 to +70°C (-40 to +158°F)
Operating / Storage humidity max. 90% RH (non-condensing)
Protection type / Protection class IP55 / I (earthed)

To top

Special features

  • The self-adhesive seal of the mounting frame prevents dust and water from entering the cabinet.
  • Functional design of the intake and exit fan hoods very effectively prevents direct intrusion of falling water and dust. The advantage is that the filter mat does not get so quickly contaminated with dirt and thus does not need to be exchanged so often.
  • The air channeling makes the filter fan particularly quiet in operation.
  • Functional and modern design enables time-saving assembly and maintenance.
  • The direction of air flow can easily be switched by reversing the axial fan (sizes 1 to 3).
  • EMC versions and other voltages on request.

To top

Filter Fan FF 018 Series

Art. No. Operating voltage Air volume, free flow Air volume with exit filter Current consumption Power consumption Average noise level (DIN EN ISO 4871) Depth in enclosure Enclosure cut-out Weight (approx.) Approvals
01800.0-00 230VAC, 50Hz 21m³/h 16m³/h 80mA 13W 31db (A) 45mm 97 x 97mm + 0.4 0.6kg VDE + UL File No. E234324
01801.0-00 230VAC, 50Hz 55m³/h 42m³/h 100mA 15W 40db (A) 58mm 125 x 125mm + 0.4 1.0kg VDE + UL File No. E234324
01802.0-00 230VAC, 50Hz 102m³/h 68m³/h 100mA 15W 39db (A) 86mm 176 x 176mm + 0.4 1.3kg VDE + UL File No. E234324
01800.0-01 120VAC, 60Hz 24m³/h 18m³/h 160mA 13W 31db (A) 45mm 97 x 97mm + 0.4 0.6kg UL File No. E234324
01801.0-01 120VAC, 60Hz 63m³/h 48m³/h 180mA 15W 40db (A) 58mm 125 x 125mm + 0.4 1.0kg UL File No. E234324
01802.0-01 120VAC, 60Hz 117m³/h 78m³/h 180mA 15W 39db (A) 86mm 176 x 176mm + 0.4 1.3kg UL File No. E234324

To top

Time-saving assembly and maintenance

STEGO´s filter fans are easily installed by one person from outside the cabinet.

1.) Make cut-out in the cabinet wall. The cut edge of the cabinet opening should be free of dirt, filings and grease. A template for the enclosure cut-out is included in the delivery of the filter fan.
2.) Remove protective film from the sealing strips on the mounting frame. Press mounting frame into the cabinet opening. The frame stays permanently in the cabinet. (For size 176mm and up we recommend additional screw fixing.)
3.) Electrically connect the axial fan using the clip connectors. Push the unit into the mounting frame. Fix using screws.
4.) Insert the filter mat in the hood. Clip on. Finished.

Changing the filter mat or fan is quickly done by one person. To change the filter mat simply remove the filter hood, insert the new mat and snap the hood back again. No tools required. Maintenance of the fan can easily be done without removing the mounting frame (2).

 

To top

Exit Filter EF 118 Series

Art. No. Depth in enclosure Enclosure cut-out Weight (approx.) Filter mat Protection type
11800.0-00 16mm 97 x 97mm + 0.4 0.3kg G4 acc. to DIN EN 779, filtering degree 94% IP55
11801.0-00 16mm 125 x 125mm + 0.4 0.4kg G4 acc. to DIN EN 779, filtering degree 94% IP55
11802.0-00 16mm 176 x 176mm + 0.4 0.6kg G4 acc. to DIN EN 779, filtering degree 94% IP55

To top

Filter Mat FM 086

Filter mat 89 x 89mm 118 x 118mm 168 x 168mm
G4 (1 packaging unit = 3 pcs.) Art. No. 08600.0-00 Art. No. 08601.0-00 Art. No. 08602.0-00

To top

Technical Drawing

Filter Fan 018 Series

To top

Search 

STEGO UK Ltd

Unit 12, First Quarter
Bus. Park
Blenheim Road
Epsom
Surrey KT19 9QN
England

Tel. +44 (0)1372 747250
Fax +44 (0)1372 729854

E-Mail: info(at)stego.co.uk

update: 3. January 2012 15:52

Search engine | Legal Notices | Sitemap | AGBs