Mechanical Thermostat FZK 011 Series

  • Adjustable temperature
  • High switching capacity
  • Small hysteresis
  • Change-over contact
  • Clip fixing

The mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices. The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact. Due to the integrated thermal feedback the switch temperature difference could be reduced. Functionality: The temperature setting on the scale equals to the upper switch point, which means that the NC contact opens. The temperature setting minus switch temperature difference (and tolerances) equals to the lower switch point, which means that the NC contact closes.

Technical Data

>> Download PDF

Switch temperature difference 5K (-3/+2K tolerance)¹
Sensor element thermostatic bimetal
Contact type change-over snap-action contact
Service life > 100,000 cycles
Min. switching capacity 10mA
Max. switching capacity, NC 250VAC, 10 (4) A
  120VAC, 10 (4) A
  30WDC
Max. switching capacity, NO 250VAC, 5 (2) A
  120VAC, 5 (2) A
  30WDC
Max. inrush current 16AAC for 10 sec.
Connection² 4-pole terminal, clamping torque 0.5Nm max.:
  rigid wire 2.5mm²
  stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 38mm
Weight approx. 0.1kg
Fitting position variable
Operating / Storage temperature -45 to +65°C (-49 to +149°F)
Operating / Storage humidity max. 90% RH (non-condensing)
Protection type IP20
Approvals UL File No. E164102

¹ If the Normally Closed contact is used, the switch temperature difference could be reduced by connecting terminal "N" (RF heating resistor). It causes the thermal feedback which is subject to surrounding conditions and thus has to be determined for each individual application.

² When connecting with wires, wire end ferrules must be used.

Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and / or self-heating of the contacts.

To top

Art. No. Operating voltage Setting range
01170.0-00 230VAC +5 to +60°C
01170.0-01 230VAC +40 to +140°F
01170.0-02 230VAC -20 to +35°C
01170.9-00 120VAC +40 to +140°F
01170.9-01 120VAC +5 to +60°C

To top

Technical Drawing

To top

Search 

STEGO UK Ltd

Unit 12, First Quarter
Bus. Park
Blenheim Road
Epsom
Surrey KT19 9QN
England

Tel. +44 (0)1372 747250
Fax +44 (0)1372 729854

E-Mail: info(at)stego.co.uk

Last updated: 26. April 2012 14:11

Patent Info | Legal Notices | Conditions of Sale | Search engine | Sitemap